Permit Number: T10EL00907
Parcel: 99999999B

Address:
6701 S TUCSON BL

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL00907
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/23/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Billboard: T10EL00907, 6701 S Tucson BL

1. How will transition be on 1/2" conduit to 3/4" conduit on Sheet 2 of 3. on Elevation. Several instances.

Ray T Majuta, Elect Pln Ck,
PDSD, C of Tuc,
4/24/10
520-837/4988
04/28/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approved Please find below comments on the lighting relocation & electrical repair
submittal for COT ID# 273 at 6701 South Tucson Boulevard (T10EL00907). All
comments are "for future reference only" and, as to BRC review, the plan set
is ready for final approval and permit issuance.

Mark Mayer
Billboard Review Committee
3361 East 23rd Street
Tucson, Arizona 85713
520.326.4522

Sheet 1

1. Comment for future reference only: Billboard Notes (#5): change "Faces"
to "faces".
2. Comment for future reference only: Billboard Notes (#11): delete comma
after "relocated".
3. Comment for future reference only: Title Block: change title to
"Lighting Relocation and Electrical Repair Site Plan".
4. Comment for future reference only: delete "COT Activity No. __________"
under the title block (as per 4/27/10 meeting; retain for resubmittals
only).

Sheet 2

1. Comment for future reference only: delete "COT Activity No. __________"
in the title block (as per 4/27/10 meeting; retain for resubmittals only).
2. Comment for future reference only: Title Block: change title to
"Lighting Relocation and Electrical Repair Plan" and delete quotation marks.
3. Comment for future reference only: Side View: add dimension between top
stringer and top of upright/face panel (alternatively, depict all four
stringers).

Sheet 3

1. Comment for future reference only: delete "COT Activity No. __________"
in the title block (as per 4/27/10 meeting; retain for resubmittals only).
2. Comment for future reference only: Title Block: change title to
"Lighting Relocation and Electrical Repair Plan" and delete quotation marks.
3. Comment for future reference only: Mounting Detail (3rd on right):
indicate as side view & conform vertical location of unistrut to Mounting
Detail Rear Elevation (the former shows the unistrut top flush with the
stringer top while the latter shows the unistrut top one inch (+/-) below
the stringer top); also bring scale of 6" wood stringer more into scale with
7' unistrut and three details more into scale with each other.
4. Comment for future reference only: Side View: add dimension between top
stringer and top of upright/face panel (alternatively, depict all four
stringers).

Final Status

Task End Date Reviewer's Name Type of Review Description
05/12/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
05/12/2010 SUE REEVES REJECT SHELF Completed