Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD-BLDG/ELEC10days
Permit Number - T10EL00907
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/21/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/23/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Billboard: T10EL00907, 6701 S Tucson BL 1. How will transition be on 1/2" conduit to 3/4" conduit on Sheet 2 of 3. on Elevation. Several instances. Ray T Majuta, Elect Pln Ck, PDSD, C of Tuc, 4/24/10 520-837/4988 |
| 04/28/2010 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Approved | Please find below comments on the lighting relocation & electrical repair submittal for COT ID# 273 at 6701 South Tucson Boulevard (T10EL00907). All comments are "for future reference only" and, as to BRC review, the plan set is ready for final approval and permit issuance. Mark Mayer Billboard Review Committee 3361 East 23rd Street Tucson, Arizona 85713 520.326.4522 Sheet 1 1. Comment for future reference only: Billboard Notes (#5): change "Faces" to "faces". 2. Comment for future reference only: Billboard Notes (#11): delete comma after "relocated". 3. Comment for future reference only: Title Block: change title to "Lighting Relocation and Electrical Repair Site Plan". 4. Comment for future reference only: delete "COT Activity No. __________" under the title block (as per 4/27/10 meeting; retain for resubmittals only). Sheet 2 1. Comment for future reference only: delete "COT Activity No. __________" in the title block (as per 4/27/10 meeting; retain for resubmittals only). 2. Comment for future reference only: Title Block: change title to "Lighting Relocation and Electrical Repair Plan" and delete quotation marks. 3. Comment for future reference only: Side View: add dimension between top stringer and top of upright/face panel (alternatively, depict all four stringers). Sheet 3 1. Comment for future reference only: delete "COT Activity No. __________" in the title block (as per 4/27/10 meeting; retain for resubmittals only). 2. Comment for future reference only: Title Block: change title to "Lighting Relocation and Electrical Repair Plan" and delete quotation marks. 3. Comment for future reference only: Mounting Detail (3rd on right): indicate as side view & conform vertical location of unistrut to Mounting Detail Rear Elevation (the former shows the unistrut top flush with the stringer top while the latter shows the unistrut top one inch (+/-) below the stringer top); also bring scale of 6" wood stringer more into scale with 7' unistrut and three details more into scale with each other. 4. Comment for future reference only: Side View: add dimension between top stringer and top of upright/face panel (alternatively, depict all four stringers). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/12/2010 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 05/12/2010 | SUE REEVES | REJECT SHELF | Completed |