Permit Number: T10EL00906
Parcel: 10512020C

Address:
4144 N ORACLE RD

Review Status: Active

Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL00906
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/17/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/27/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond As this review was previously approved, the comments below can be considered "for future reference" only.


Please find below comments on the lighting relocation & electrical repair
resubmittal for COT ID# 488 at 4144 North Oracle Road (T10EL00906).

Mark Mayer
Billboard Review Committee
3361 East 23rd Street
Tucson, Arizona 85713
520.326.4522

Sheet 2 of 3

1. Note: add notation that no junction boxes to be installed or used other
than those depicted on plan.

2. Note: add notation that number of #12 conductors specified includes
ground wire.

3. Partial Plan View: use this top view (enlarged if necessary) to provide
a full schematic of all junction boxes and connecting conduit; a note that
there is a junction box under each of the depicted ballasts will suffice for
those junction boxes; in particular, depict the junction box where the
circuits will branch for the two different faces, including its specific
location and the change in number of conductors (use Elevation to show
specific location of this branch junction box as well); alternatively, a
three dimensional schematic showing the junction box layout may be provided
(including ballasts and the changes in number of conductors).

4. Elevation: clarify what "NEW 90º" depicted is and its relation to the ½"
liquid tite; show liquid tite in curved form (as in other submittals) or
clarify why liquid tite is depicted in 90º configuration.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/25/2010 SUE REEVES REJECT SHELF RECEIVED