Permit Number: T10EL00906
Parcel: 10512020C

Address:
4144 N ORACLE RD

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL00906
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/23/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Billboard: T10EL00906
4144 N Oracle Rd.,
Electrical denied for following:

1. How will electrical transition from 1/2" to 3/4" on Sheet 2 of 3, Elevation.

Ray T Majuta, El Pln Ck,
PDSD C of Tuc,
4/24/10
520-837/4988
04/28/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond Please find below comments on the lighting relocation & electrical repair
submittal for COT ID# 488 at 4144 North Oracle Road (T10EL00906). All
comments are "for future reference only" and, as to BRC review, the plan set
is ready for final approval and permit issuance. Note, however, that at
least one existing lamp on this billboard is high ouput (HO) and approval of
this application is based on Clear Channel's agreement to lamp/ballastst
standardization at the meeting yesterday where 10.5x36 and 10x40 billboards
would be limited to HO (subject to consulttation with Clear Channel sales
staff).

Mark Mayer
Billboard Review Committee
3361 East 23rd Street
Tucson, Arizona 85713
520.326.4522

Sheet 1

1. Comment for future reference only: Billboard Notes (#5): change "Faces"
to "faces".
2. Comment for future reference only: Billboard Notes (#11): delete comma
after "relocated".
3. Comment for future reference only: Title Block: change title to
"Lighting Relocation and Electrical Repair Site Plan".
4. Comment for future reference only: delete "COT Activity No. __________"
under the title block (as per 4/27/10 meeting; retain for resubmittals
only).

Sheet 2

1. Comment for future reference only: delete "COT Activity No. __________"
in the title block (as per 4/27/10 meeting; retain for resubmittals only).
2. Comment for future reference only: Title Block: change title to
"Lighting Relocation and Electrical Repair Plan" and delete quotation marks.

Sheet 3

1. Comment for future reference only: delete "COT Activity No. __________"
in the title block (as per 4/27/10 meeting; retain for resubmittals only).
2. Comment for future reference only: Title Block: change title to
"Lighting Relocation and Electrical Repair Plan" and delete quotation
marks.
3. Comment for future reference only: Mounting Detail (3rd on right):
indicate as side view & conform location of unistrut top to that shown in
Mounting Detail-Rear Elevation View (the former shows the unistrut top flush
with the stringer top while the latter shows the unistrut top one inch (+/-)
below the stringer top); also bring three details more into scale with each
other.
4. Comment for future reference only: Mounting Detail-Rear Elevation View:
delete dotted line on stringer (for angle iron only).
5. Comment for future reference only: Side View: add dimension between top
stringer and top of upright/face panel (alternatively, depict all four
stringers).

Final Status

Task End Date Reviewer's Name Type of Review Description
05/12/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
05/12/2010 CINDY AGUILAR REJECT SHELF Completed