Permit Number: T10EL00835
Parcel: 99999999B

Address:
2112 E BENSON HY

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL00835
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond BRC Comments

Below are comments on the 8/10/10 lighting relocation & electrical repair
resubmittal for COT ID# 8 at 2112 East Benson Highway (T10EL00835).


Original Sheet 2

1. Lack of comments on the original Sheet 2 was based on the four
replacement conductors leaving the panel box including the ground as per
earlier convention in administering the settlement agreement; prior to
permit issuance, a notation needs to be added to Sheet 2 clarifying that the
four conductors include one ground and that the three remaining conductors
provide for two circuits (two hot & one nuetral).

Sheet 3

No comments.
09/07/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
09/07/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/08/2010 CINDY AGUILAR OUT TO CUSTOMER Completed