Permit Number: T10EL00835
Parcel: 99999999B

Address:
2112 E BENSON HY

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL00835
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/19/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied COMMENTS ON LIGHTING RELOCATION & ELECTRICAL REPAIR SUBMITTAL FOR CLEAR
CHANNEL BILLBOARD COT ID #8 AT 2112 EAST BENSON HIGHWAY

Lighting Relocation and Repair Site Plan (Sheet 1 of 1)

1. Comment for future reference: Billboard Notes (#4): opening line should
be amended to read "Latitude and Longitude of billboard at approximate
center of footprint:" (also deleting line at bottom).
2. Comment for future reference: Billboard Notes (#5): change "Faces" to
"faces".
3. Comment for future reference: Billboard Notes (#11): delete comma after
"relocated".
4. Comment for future reference: Title Block: change title to "Lighting
Relocation and Electrical Repair Site Plan".
5. Comment for future reference: as to "COT Activity No. __________" under
the title block, not much space is left to insert the handwritten number;
this entry may be better located, as per PDSD staff direction, at the upper
right of the plan sheet where such activity numbers are more typically
entered; the Site Plan Requirements should be amended in this regard and to
also state a minimum font size that approximates the handwritten entries.

Lighting Relocation and Repair Plan (Sheet 2 of 3)

1. Comment for future reference: Title Block: change to "COT Activity No.
T10EL00835" (and move to more appropriate location as determined by PDSD
staff).
2. Comment for future reference: Title Block: change title to "Lighting
Relocation and Electrical Repair Plan" and delete quotation marks.
3. Comment for future reference: Note (Bullet #2): indicate ¾" rigid
conduit as "new".
4. Comment for future reference: Elevation: depict ballasts in existing
locations (in addition to new locations).

Lighting Relocation and Repair Plan (Sheet 3 of 3)

1. Change to "COT Activity No. T10EL00835" (and move to more appropriate
location as determined by PDSD staff).
2. Title Block: change title to "Lighting Relocation and Electrical Repair
Plan Detail" and delete quotation marks.
3. Side View & Mounting Detail: change depiction of stringers from angle
iron to wood. (this billboard has wood stringers for both faces).
4. Side View & Mounting Detail: show appropriate mounting (straps) for wood
stringers.
04/19/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/11/2010 DELMA ROBEY OUT TO CUSTOMER Completed
08/11/2010 SUE REEVES REJECT SHELF Completed