Permit Number: T10EL00831
Parcel: 140420400

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL00831
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/19/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied COMMENTS ON LIGHTING RELOCATION & ELECTRICAL REPAIR SUBMITTAL FOR CLEAR
CHANNEL BILLBOARD COT ID #261 AT 2334 EAST VALENCIA ROAD

Lighting Relocation and Repair Site Plan (Sheet 1 of 1)

1. Comment for future reference: Billboard Notes (#4): opening line should
be amended to read "Latitude and Longitude of billboard at approximate
center of footprint:" (also deleting line at bottom).
2. Comment for future reference: Billboard Notes (#5): change "Faces" to
"faces".
3. Comment for future reference: Billboard Notes (#11): delete comma after
"relocated".
4. Comment for future reference: Title Block: change title to "Lighting
Relocation and Electrical Repair Site Plan".
5. Comment for future reference: as to "COT Activity No. __________" under
the title block, not much space is left to insert the handwritten number;
this entry may be better located, as per PDSD staff direction, at the upper
right of the plan sheet where such activity numbers are more typically
entered; the Site Plan Requirements should be amended in this regard and to
also state a minimum font size that approximates the handwritten entries.

Lighting Modification and Repair Plan (Sheet 2 of 3)

1. Change to "COT Activity No. T10EL00831" (and move to more appropriate
location as determined by PDSD staff).
2. Notes (Bullet #2): indicate ¾" rigid conduit as "new".
3. Title Block: change title to "Lighting Relocation and Electrical Repair
Plan" and delete quotation marks.
4. Scope of Work: indicate whether wood section panels or other
non-electrical parts will be removed and reinstalled to gain access for
light support arm mounting and if so describe the removal and reinstallation
and provide detail of such parts.
5. Elevation: depict ballasts in existing locations.

Lighting Relocation and Repair Plan (Sheet 3 of 3)

1. Change to "COT Activity No. T10EL00831" (and move to more appropriate
location as determined by PDSD staff).
2. Title Block: change title to "Lighting Relocation and Electrical Repair
Plan Detail" and delete quotation marks.
3. Mounting Detail: show detail of mounting bracket in three views with
dimensions.
04/19/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/12/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
05/12/2010 SUE REEVES REJECT SHELF Completed