Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/19/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10EL00830, (Billboard)

Denied, show how transition is made on Sheet 2 of 3, on 1/2" EMT conduit to3/4" Rigid conduit to fixtures.

Ray T Majuta, PDSD,City of Tucson,
Elect Plan Review,4/20/10
520-837/4988
05/03/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Please find below comments on the lighting modification & electrical repair
submittal for COT ID# 120 at 6632 East Tanque Verde Road (T10EL00830).

Mark Mayer
Billboard Review Committee
3361 East 23rd Street
Tucson, Arizona 85713
520.326.4522

Sheet 1 of 3

1. Comment for future reference only: Billboard Notes (#4): opening line
should be amended to read "Latitude and Longitude of billboard at
approximate center of footprint:" (also deleting line at bottom).
2. Comment for future reference only: Billboard Notes (#5): change "Faces"
to "faces".
3. Comment for future reference only: Billboard Notes (#11): delete comma
after "relocated".
4. Comment for future reference only: Title Block: change title to
"Lighting Modification and Electrical Repair Site Plan".
5. Comment for future reference only: delete "COT Activity No. __________"
under the title block (as per 4/27/10 meeting; retain for resubmittals only
at revised location).

Sheet 2 of 3

1. Title Block: enter T10EL00830 into COT Activity No. blank.
2. Title Block: change title to "Lighting Modification and Electrical
Repair Plan" and delete quotation marks.
3. Note (Bullet #2): indicate ¾" rigid conduit as "new".
4. Note (Bullet #3): indicate HO lamp with matching specifications
5. Note (Bullet #5): indicate ballast to match HO (800 ma).

Sheet 3 of 3

1. Title Block: enter T10EL00830 into COT Activity No. blank.
2. Title Block: change title to "Lighting Modification and Electrical
Repair Plan Detail" and delete quotation marks.
3. Mounting Detail: show detail of mounting bracket in three views with
dimensions (assure that vertical position of unistrut matches in all views
and that the three views are reasonably scaled to each other).
4. Description of Existing Lamp: change "Existing" to "New" and indicate HO
lamp
with matching specifications.
5. Description of Existing Ballast: indicate ballast that matches HO (800
ma).
6. Side View: add dimension between top stringer and top of upright/face
panel (alternatively, depict all four stringers).

Final Status

Task End Date Reviewer's Name Type of Review Description
06/21/2010 CPIERCE1 OUT TO CUSTOMER Completed
06/21/2010 CPIERCE1 REJECT SHELF Completed