Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10EL00752
Parcel: 99999999B

Address:
2433 E 22ND ST

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL00752
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
09/21/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
10/20/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond COT/BRC/CCO meeting is requested.

BRC Comments

Comments below are for the lighting modification & electrical repair
resubmittal (9/7/10) for COT ID# 73 at 2433 East 22nd Street (T10EL00752).

Sheet 2 of 3

1. There is no need for an additional panel and timer or 60 amp overcurrent
protection on the customer-owned utility pole; in place of the previously
existing disconnect, provide service disconnecting means per 2005 NEC
230.79(A), not to exceed 20 amps. Note that the previously existing panel
on the utility pole housed numerous breakers, indicating that this service
originally powered loads that were unrelated to the billboard and that have
long since been removed. It is questionable as to whether the electrical
connection to the billboard was ever permitted.

2. Panel Schedule: correct the volt-amp entries for Circuits #1 on the
existing 122 panel and associated sums; based on the ballast manufacturer's
stated input watts (231 watts per two lamp fixture (F96T12HO)) and the 125%
continuous load factor that the EOR includes in the panel schedule, this
figure should be no less than 577.5 v-a for that circuit for the light
fixtures alone, plus an allowance for the timer; if otherwise, provide the
calculations as to how the v-a entry was arrived at.

Sheet 3 of 3

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/21/2010 SUE REEVES APPROVAL SHELF Completed
10/21/2010 CINDY AGUILAR OUT TO CUSTOMER Completed