Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10EL00748
Parcel: 99999999B

Address:
2436 N 1ST AV

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL00748
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/12/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
04/15/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied COMMENTS ON LIGHTING RELOCATION & ELECTRICAL REPAIR SUBMITTAL FOR CLEAR
CHANNEL BILLBOARD COT ID #465 AT 2436 NORTH 1ST AVENUE

Lighting Relocation and Repair Site Plan (Sheet 1 of 1)

1. Comment for future reference: Billboard Notes (#4): opening line should
be amended to read "Latitude and Longitude of billboard at approximate
center of footprint:" (also deleting line at bottom).
2. Comment for future reference: Title Block: change title to "Lighting
Relocation and Electrical Repair Site Plan".
3. Comment for future reference: add "COT Activity No. __________" near the
title block. [Note to PDSD staff: where CCO has placed this line on
subsequent applications there is insufficient space to insert the
handwritten number; this entry may be better located at the upper right of
the plan sheet where such activity numbers are more typically written with
the Site Plan Requirements stating a minimum font size that approximates the
handwritten entries].

Lighting Relocation and Repair Plan (Sheet 2 of 3)

1. Add "COT Activity No. T10EL00748" near the title block (or at
alternative location as determined by PDSD staff).
2. Title Block: change title to "Lighting Relocation and Electrical Repair
Plan" and delete quotation marks.
3. Notes (Bullet #2): indicate ¾" rigid conduit as "new".
4. Notes (Bullets #4 & #5), Elevation & Electrical Riser Diagram: change
conduit size from ¾" EMT to ½" EMT; alternatively, retain the current
configuration as to ballast location and conduit runs except for additional
conduit runs to reach the top-mounted light fixtures.
5. Notes (Bullet #7): indicate the conduit size and type between the
ballasts and light fixtures (size should be 1/2" except for any double
bundles of
#18 wire).
6. Elevation: depict ballasts in existing locations.

Lighting Relocation and Repair Plan (Sheet 3 of 3)

1. Add "COT Activity No. T10EL00748" near the title block [or at
alternative location as determined by PDSD staff].
2. Title Block: change title to "Lighting Relocation and Electrical Repair
Plan Detail" and delete quotation marks.
3. Mounting Detail: show detail of mounting bracket in three views with
dimensions.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/07/2010 GERARDO BONILLA OUT TO CUSTOMER Completed