Permit Number: T10EL00532
Parcel: 99999999B

Address:
3712 N ORACLE RD

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL00532
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/11/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/24/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied COMMENTS ON LIGHTING RELOCATION SUBMITTAL FOR CLEAR CHANNEL BILLBOARD COT ID
#492 AT 3712 NORTH ORACLE ROAD

Lighting Removal, Replacement and/or Relocation Site Plan (Sheet 1 of 3)

1. Billboard Notes (#7; 3rd Bullet): indicate lamp manufacturer and
conform the lamp model number and the initial lumen rating to that shown on
Sheet 3.
2. Billboard Notes (#8 & #9): amend "modification" to "modification and
repair".
3. Billboard Notes (#13): after "premises", strike the balance of the
sentence and insert "except upon request in instances where the fixtures
cannot be secured on site, in which case the fixtures may be removed from
the premises only if marked for identification by a third party special
inspector approved by the City of Tucson".
4. Title Block: amend title to "Lighting Relocation Site Plan".

Electrical Plan Sheet (Sheet 2 of 3)

1. Billboard Notes (#4): add "Approximate Center of Footprint".
3. Billboard Notes (#7; 2nd Paragraph): indicate lamp manufacturer and
conform the lamp model number and the initial lumen rating to that shown on
Sheet 3.
4. Electrical Riser Diagram: indicate the size, type, and number of
conductors between the ballasts and the lamp sockets.
6. Electrical Riser Diagram: clarify the nature of the two boxes depicted
below the ballasts.
7. Title Block: add title "Lighting Relocation Site Plan".

Overhead Fluorescent Lighting (Sheet 3 of 3)

1. Top View: specify the distance of the rigid conduit run between the two
42" extensions outward from the face panels iron metal halide lighting
supports on back side of uprights to be removed.
2. Mounting Detail: clarify the substitution of pole spikes for the screws
indicated in the engineer's letter (Exhibit 8 of the Stipulation).
3. Description of New Ballast: conform to existing ballast (Universal)
shown on Sheets 1 and 2.
4. Add the street address and COT ID# to the plan sheet.
5. In lower right corner, change "Page 3 of 3" to "Sheet 3 of 3".
6. Add engineer's stamp to the plan sheet [Note: it would be preferable for
the engineer to incorporate the details from this sheet into the electrical
plan sheet].

Final Status

Task End Date Reviewer's Name Type of Review Description
03/24/2010 CPIERCE1 OUT TO CUSTOMER Completed
03/24/2010 SUE REEVES REJECT SHELF Completed