Permit Number: T10EL00531
Parcel: 99999999B

Address:
1829 N ORACLE RD

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL00531
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/11/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
06/01/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approved Please find below comments on the lighting modification & electrical repair
resubmittal for COT ID #508 at 1829 North Oracle Road (T10EL00531). Note
that for Sheet 2, only Comments #1 & #6 related to the junction box, as
newly depicted in the resubmittal (and discussed at the 5/25/10 meeting),
are holding up BRC approval at this time

Mark Mayer
Billboard Review Committee
3361 East 23rd Street
Tucson, Arizona 85713
520.326.4522

Sheet 1 of 3

1. Comment for future reference only: Billboard Notes (#13): delete this
note as not being applicable to replacement of metal halide fixtures with a
fluorescent fixtures.
2. Comment for future reference only: Title Block: change title to
"Lighting Modification and Electrical Repair Plan" (do not include quotation
marks).
3. Comment for future reference only: relocate "COT Activity No.T10EL00531"
from lower margin to standard location in title block (as per 4/27/10
meeting).

Sheet 2 of 3

1. Billboard Notes (#7; 4th Bullet): indicate elbow instead of junction box
(alternatively, indicate appropriately rated disconnect if NEC requires a
disconnect at this location).
2. Billboard Notes (#13): delete this note as it is not being applicable to
replacement of metal halide fixtures with a fluorescent fixtures.
3. Notes: add notation that number of #12 replacement conductors indicated
includes ground wire.
4. Billboard Notes: add notation that no junction boxes to be used other
than for wire connection purposes and that no junction boxes to be installed
or remain other than those depicted on the plan.
5. Notes: add notation that number of #12 replacement conductors indicated
includes ground wire.
6. Partial Riser Diagram (Existing I-Beam of Structure) & Partial Plan
View: delete junction box and insert elbow (alternatively, insert
appropriately rated disconnect if NEC requires a disconnect at this
location)
7. Title Block: amend title to "Lighting Modification & Electrical Repair
Site Plan".

Sheet 3 of 3

1. Comment for future reference only: Title Block: change title to
"Lighting Modification and Electrical Repair Plan" (do not include quotation
marks).

Final Status

Task End Date Reviewer's Name Type of Review Description
06/10/2010 DELMA ROBEY OUT TO CUSTOMER Completed
06/10/2010 SUE REEVES REJECT SHELF Completed