Permit Number: T10EL00531
Parcel: 99999999B

Address:
1829 N ORACLE RD

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL00531
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/11/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/17/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied COMMENTS ON LIGHTING MODIFICATION & REPAIR SUBMITTAL FOR CLEAR CHANNEL
BILLBOARD COT ID #508 AT 1829 NORTH ORACLE ROAD

Lighting Removal, Replacement and/or Relocation Site Plan (Sheet 1 of 3)

1. Billboard Notes (#7; 1st Bullet): add removal of horizontal light arm
supports.
2. Billboard Notes (#7; 3rd Bullet): indicate lamp manufacturer and
conform the lamp model number and the initial lumen rating to that shown on
Sheet 3.
3. Billboard Notes (#8): amend "modification" to "modification and repair".
4. Title Block: amend title to "Lighting Modification & Repair Site Plan".

Electrical Plan Sheet (Sheet 2 of 3)

1. Billboard Notes (#4): add "Approximate Center of Footprint".
2. Billboard Notes (#7; 2nd Paragraph): indicate the lamp manufacturer and
conform the lamp model number and the initial lumen rating to that shown on
Sheet 3.
3. Partial Riser Diagram: indicate the size, type, and number of conductors
between the ballast and the lamp sockets.
4. Partial Riser Diagram & Elevations: indicate the size, type, and number
of conductors between the meter and the weatherhead.
5. Partial Riser Diagram & Elevations: clarify why ¾" EMT conduit is being
shown where ½" EMT conduit should be adequate for a single ballast/single
fixture application; if changed to ½" EMT on plans, conform same in
Billboard Notes on Sheets 1 & 2 (#7; 4th Bullet/3rd Paragraph) and Back View
on Sheet 3.
6. Title Block: amend title to "Lighting Modification & Repair Site Plan".

Overhead Fluorescent Lighting (Sheet 3 of 3)

1. Description of New Ballast: conform ballast information to that in Scope
of Work in Sheets 1 & 2.
2. End View: delete the upper backrail on back side of uprights.
3. Mounting Detail: clarify the substitution of pole spikes for the screws
indicated in the engineer's letter (Exhibit 8 of the Stipulation).
4. End View: add dimension for distance that fixture extends horizontally
from point of attachment.
5. Back View: add length dimension for the light fixture.
6. Add the street address and COT ID# to the plan sheet.
7. Add engineer's stamp to the plan sheet [Note: it would be preferable for
the engineer to incorporate the details from this sheet into the electrical
plan sheet].

Final Status

Task End Date Reviewer's Name Type of Review Description
04/30/2010 CPIERCE1 OUT TO CUSTOMER Completed
04/30/2010 SUE REEVES REJECT SHELF Completed