Permit Number: T10EL00530
Parcel: 11207146B

Address:
2601 E GRANT RD

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL00530
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/11/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
04/09/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied COMMENTS ON LIGHTING MODIFICATION & REPAIR SUBMITTAL FOR CLEAR CHANNEL
BILLBOARD COT ID #439 AT 2601 EAST GRANT ROAD

Lighting Removal, Replacement and/or Relocation Site Plan (Sheet 1 of 3)

1. Billboard Notes (#7; 3rd Bullet): indicate lamp manufacturer and
conform the lamp model number and the initial lumen rating to that shown on
Sheet 3.
2. Billboard Notes (#8 & #9): amend "modification" to "modification and
repair".
3. Title Block: amend title to "Lighting Modification & Repair Site Plan".

Electrical Plan Sheet (Sheet 2 of 3)

1. Billboard Notes (#4): add "Approximate Center of Footprint".
3. Billboard Notes (#7; 2nd Paragraph): indicate lamp manufacturer and
conform the lamp model number and the initial lumen rating to that shown on
Sheet 3.
4. Electrical Riser Diagram: indicate the size, type, and number of
conductors between the ballasts and the lamp sockets.
6. Electrical Riser Diagram: clarify the nature of the two boxes depicted
below the ballasts.
7. Electrical Riser Diagram: indicate the manufacturer and model number for
the replacement meter socket box.
8. Title Block: add title "Lighting Modification & Repair Site Plan".

Overhead Fluorescent Lighting (Sheet 3 of 3)

1. Top View: specify the distance of the rigid conduit run between the two
42" extensions outward from the face panels iron metal halide lighting
supports on back side of uprights to be removed.
2. Mounting Detail: clarify the substitution of pole spikes for the screws
indicated in the engineer's letter (Exhibit 8 of the Stipulation).
3. Add the street address and COT ID# to the plan sheet.
4. In lower right corner, change "Page 3 of 3" to "Sheet 3 of 3".
5. Add engineer's stamp to the plan sheet [Note: it would be preferable for
the engineer to incorporate the details from this sheet into the electrical
plan sheet].

Final Status

Task End Date Reviewer's Name Type of Review Description
04/22/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
04/22/2010 SUE REEVES REJECT SHELF Completed