Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10EL00460
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied COMMENTS ON LIGHTING MODIFICATION RESUBMITTAL FOR CLEAR CHANNEL BILLBOARD
COT ID #573 AT 846 NORTH STONE AVENUE

General Note: Except for Comment #1 on Sheet 2 (Electrical Riser Diagram)
and Comment #1 on Sheet 3 (End View), all of these comments are related to
consistent form as to amended site plan requirements (per the March 30, 2010
meeting). They are not intended to indicate necessary revisions on Sheet 1
other than to the extent CCO chooses to make such revisions and resubmit
that sheet as well.

Lighting Removal, Modification and/or Replacement Site Plan (Sheet 1 of 3)

1. Billboard Notes (#13): delete this note.
2. Title Block: amend title to "Lighting Modification Site Plan". [Note:
since the conduit is being downsized to match the conductors, this would be
considered a "modification plan" and not a "modification & repair" plan]
3. Add "COT Activity No. T10EL00460" in appropriate location.

Electrical Plan Sheet (Sheet 2 of 3)

1. Electrical Riser Diagram: change reference in cloud from "single gang
outlet box to "single gang junction box".
2. Billboard Note #4: change opening line to read "Latitude and Longitude
of billboard at approximate center of footprint:" (also deleting line at
bottom of note).
3. Billboard Notes (#13): delete this note.
4. Title Block: add appropriate title in title space ("Lighting
Modification Plan").
5. Title Block: change "2 of 3" to "Sheet 2 of 3".
6. Add "COT Activity No. T10EL00460" in appropriate location.

Overhead Fluorescent Lighting (Sheet 3 of 3)

1. End View: designate the bottom angle iron light arm support on
back side of uprights to be removed (consistent with the Billboard Note #7
on Sheets 1 & 2); also depict the existing wood 3" x 4" backrail located
between
the two light arm supports [Note: The BRC would not object to the existing
3" x 4" wood back rail being replaced, repositioned, or replaced and
repositioned under this permit].
2. Title Block: add appropriate title in title space ("Lighting
Modification Plan Detail").
3. Title Block: change "2 of 3" to "Sheet 2 of 3".
4. Add "COT Activity No. T10EL00460" in appropriate location.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/09/2010 DELMA ROBEY OUT TO CUSTOMER Completed
04/09/2010 SUE REEVES REJECT SHELF Completed