Permit Number: T10EL00460
Parcel: 117031000

Address:
846 N STONE AV

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC

Permit Number - T10EL00460
Review Name: BILLBOARD-BLDG/ELEC
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/04/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/15/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied 3/17/10
Amended comments below.

AMENDED COMMENTS ON LIGHTING MODIFICATION & REPAIR SUBMITTAL FOR CLEAR
CHANNEL BILLBOARD COT ID #573 AT 846 NORTH STONE AVENUE

Lighting Removal, Modification and/or Replacement Site Plan (Sheet 1 of 3)

1. Billboard Notes (#7; 3rd Bullet): add lamp manufacturer and conform the
lamp model number and the initial lumen rating to that shown on Sheet 3.
2. Billboard Notes (#8): amend to "modification and repair".
3. Title Block: amend title to "Lighting Modification & Repair Plan".

Electrical Plan (Sheet 2 of 3)

1. Add notation that reads "No parts or components are to be removed,
installed, replaced, or reinstalled except as indicated".
2. Billboard Notes (#4): add "Approximate Center of Footprint"
3. Billboard Notes (#7; 2nd Paragraph): indicate the lamp manufacturer and
conform the lamp model number and the initial lumen rating to that shown on
Sheet 3.
4. Electrical Riser Diagram: indicate the size, type, and number of
conductors between the ballast and the lamp sockets.
5. Electrical Riser Diagram: clarify why ¾" EMT conduit is being shown
where ½" EMT conduit should be adequate for a single ballast/single fixture
application; if changed to ½" EMT on plans, conform same in Billboard Notes
on Sheets 1 & 2 (#7; 4th Bullet/3rd Paragraph) and Back View on Sheet 3.
6. Electrical Riser Diagram: clarify the nature of the box depicted below
the ballast.
7. Partial Plan View: describe on plan the existing & replacement controls
to be replaced; also include replacement in scope of work (Billboard Note
#7).
8. Partial Plan View & Partial Vicinity Map: each detail shows a
double-faced billboard; conform to the single-faced billboard indicated in
the Billboard Notes.
9. Title Block: add title "Lighting Modification & Repair Plan").

Overhead Fluorescent Lighting (Sheet 3 of 3)

1. Description of Existing Lamp: indicate lamp manufacturer.
2. End View: designate the two angle iron metal halide lighting supports on
back side of uprights to be removed.
3. Mounting Detail: clarify the substitution of pole spikes for the screws
indicated in the engineer's letter (Exhibit 8 of the Stipulation).
4. End View: add dimension for distance that fixture extends horizontally
from point of attachment.
5. Back View: add length dimension for the light fixture.
6. Add the street address and COT ID# to the plan sheet.
7. The sheet needs to be stamped by the engineer [Note: it would be
preferable for the engineer to incorporate the details from this sheet into
the electrical plan sheet].




Original 3/12/10 comments below.

COMMENTS ON LIGHTING DEMOLITION/REPLACEMENT SUBMITTAL FOR CLEAR CHANNEL
BILLBOARD COT ID #573 AT 846 NORTH STONE AVENUE

Billboard Modification Site Plan (Sheet 1 of 3)

No comments.

Electrical Plan Sheet (Sheet 2 of 3)

1. Add notation that reads "No parts or components are to be removed,
installed, replaced, or reinstalled except as shown on plans".
2. Billboard Notes (#4): indicate the manufacturer of the lamp.
3. Billboard Notes (#7): clarify the initial lumen rating (8434 shown as
compared to 8430 on Sheet 3).
4. Electrical Riser Diagram: indicate the size, type, and number of
conductors between the ballast and the lamp sockets. [Note: if six #14
wires are used as in previous fluorescent submittal, then ½" conduit
is adequate].
5. Electrical Riser Diagram: clarify why ½" EMT conduit is being upgraded
to ¾" EMT conduit; if changed to ½" on plans, conform same on Sheet 1 and
Sheet 3 [Note: if six #14 or #18 wires per ballast are used as in
respective previous fluorescent submittals, then ½" conduit is adequate for
this single ballast application]
6. Electrical Riser Diagram: clarify the nature of the box depicted below
the ballast.
7. Partial Plan View: describe on plan the existing & replacement controls
to be replaced; also include replacement in scope of work (Billboard Note
#7).
8. Partial Plan View & Partial Vicinity Map: each detail shows a
double-faced billboard; conform to the single-faced billboard indicated in
the Billboard Notes.
9. Title Block: add appropriate title in title space (e.g., "Lighting
Demolition & Replacement Plan").

Overhead Fluorescent Lighting (Sheet 3 of 3)

1. Description of Existing Lamp: indicate lamp manufacturer. [Note: the
model number is unique to Sylvania]
2. End View: designate the two angle iron metal halide lighting supports on
back side of uprights to be removed.
3. Mounting Detail: clarify the substitution of pole spikes for the screws
indicated in the engineer's letter (Exhibit 8 of the Stipulation).
4. End View: add dimension for distance that fixture extends horizontally
from point of attachment.
5. Back View: add length dimension for the light fixture.
6. Add the street address and COT ID# to the plan sheet.
7. The sheet needs to be stamped by the engineer [Note: it would be
preferable for the engineer to incorporate the details from this sheet into
the electrical plan sheet].

Final Status

Task End Date Reviewer's Name Type of Review Description
03/24/2010 CPIERCE1 OUT TO CUSTOMER Completed
03/24/2010 SUE REEVES REJECT SHELF Completed