Permit Number: T10EL00450
Parcel: 11016221A

Address:
6255 E GRANT RD

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T10EL00450
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Denied, the Outdoor Lighting Calculations do not include the new lights added . The calculation provided is the same as permit T08CM03587. a permit which has been finaled. Redo the new calculation , verify compliance and resubmit.

Ray T Majuta
3/3/10, PDSD
Ray.Majuta@tucsonaz.gov



Plans denied for review 3/11/10, for following:

1. Recalculation on lumens allows for 10- 400 watt fixtures to be installed, 12 exist on site installed, only 10 can be installed. Correct plans, lumen count and notes on plan to reflect correct allowed installation.

Ray T Majuta, 3/11/10