Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T10EL00450
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/03/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Denied, the Outdoor Lighting Calculations do not include the new lights added . The calculation provided is the same as permit T08CM03587. a permit which has been finaled. Redo the new calculation , verify compliance and resubmit. Ray T Majuta 3/3/10, PDSD Ray.Majuta@tucsonaz.gov Plans denied for review 3/11/10, for following: 1. Recalculation on lumens allows for 10- 400 watt fixtures to be installed, 12 exist on site installed, only 10 can be installed. Correct plans, lumen count and notes on plan to reflect correct allowed installation. Ray T Majuta, 3/11/10 |