01/21/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved Project: T10EL00121
8060 E Research Lp


1. The equipment ground between the main 200 amp disconnect and the CT can required to be rated per 2005 NEC 250-66,not 250-122.
2. The plan shows a 100 amp disconnect at the Grinder, should be 30 amp.