Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10EL00121
Parcel: 13507457A

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T10EL00121
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved Project: T10EL00121
8060 E Research Lp


1. The equipment ground between the main 200 amp disconnect and the CT can required to be rated per 2005 NEC 250-66,not 250-122.
2. The plan shows a 100 amp disconnect at the Grinder, should be 30 amp.

Ray T Majuta
PDSD City of Tucson,
Elect PLn Ck
1/21/10
520-837-4988