Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM03545
Parcel: 113100010

Address:
1545 E COPPER ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T10CM03545
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET C2.3; SECTION 1: WALLS OVER 6' IN HEIGHT REQUIRE STRUCTURAL CALCULATIONS FOR THE WALL AND THE FOOTING. PROVIDE.
01/11/2011 DAVID RIVERA ZONING REVIEW Approved
01/18/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T10CM03545
1545 E Copper ST
Electrical Site Upgrade

Electrical needs following information in order to approve,
1. Provide information sheets on SES, Sectionalizers, Transformers and Ground Mount Pull boxes.
2. Service Entrance Conductors coming into SES listed as 300 mcm only, these also to be rated for MV ?
3. How are the conductors at the secondary side of the SES protected per NEC. Note 10 indicates setting adjustment ?
4. Sheet E2.0 keynote #5, shows 3-750 mcm 5 kv MV 105 conductors, after the Sectionalizers they drop to 3/0 5kv MV-105, are the Secontionalizers provided with ant overcurrent protection ? If so please provide type to be used.


Ray T Majuta,
PDSD, City of Tucson,
Elect Pln Ck,
1/21/11
12/27/2010 DAVE MANN FIRE REVIEW Approved
12/27/2010 LOREN MAKUS ENGINEERING REVIEW Approved Floodplain not required per JE Fuller report.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/03/2011 DELMA ROBEY OUT TO CUSTOMER Completed
02/03/2011 SUE REEVES REJECT SHELF Completed