Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T10CM03530
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/05/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Please provide and identify accessible seatings in the dininga nd lounge areas as per 2006 IBC, Section 1108.2. 2. Please identify the Meeting Room and Exercise areas to be remodeled on detail 1/G004. END OF REVIEW |
| 01/12/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/12/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide cleanouts in the vent pipes to allow for rodding of all island vent pipes located below the flood rim of the sink being drained. Reference: Section 913.3, IPC 2006. 2. Clarify detail 1/P101 by showing the drain and vent pipe sizes to be used. Reference: Section 106.3.1, IPC 2006. |
| 01/12/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify the intent of sheet M102; two flag notes are listed but only one is shown on the plans. Reference: Section 106.3.1, IMC 2006. 2. Specify the minimum resistance (R-value) of the new duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson. |
| 01/13/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10CM03530 2505 E Executive Dr Interior Remodel The electrical plans have been denied for the following: 1. Sheet 100, identify circuits for lighting being relocated and new. Identify panel fed from and it's location. Provide panels schedules and modified loads. 2. Provide cut sheets for new dimmers to be used.Identify which circuits will be used by which dimmers. 3. Show on plan which lights will be on which zone. 4. Sheet E201, Identify circuits to all power being relocated or added, provide panel locations, schedules and modified loads. 5. Provide the same as #4 for sheets E210 and E400. Ray Majuta,Elect Plan Review, PDSD, City of Tucson, 1/17/11, Ray.Majuta@tucsonaz.gov |
| 12/21/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/22/2010 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/07/2011 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 02/07/2011 | SUE REEVES | REJECT SHELF | Completed |