Permit Number: T10CM03530
Parcel: 140420870

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T10CM03530
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide and identify accessible seatings in the dininga nd lounge areas as per 2006 IBC, Section 1108.2.
2. Please identify the Meeting Room and Exercise areas to be remodeled on detail 1/G004.
END OF REVIEW
01/12/2011 ROBERT SHERRY WATER REVIEW Approved
01/12/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide cleanouts in the vent pipes to allow for rodding of all island vent pipes located below the flood rim of the sink being drained. Reference: Section 913.3, IPC 2006.
2. Clarify detail 1/P101 by showing the drain and vent pipe sizes to be used. Reference: Section 106.3.1, IPC 2006.
01/12/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the intent of sheet M102; two flag notes are listed but only one is shown on the plans. Reference: Section 106.3.1, IMC 2006.
2. Specify the minimum resistance (R-value) of the new duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
01/13/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM03530
2505 E Executive Dr
Interior Remodel

The electrical plans have been denied for the following:

1. Sheet 100, identify circuits for lighting being relocated and new. Identify panel fed from and it's location. Provide panels schedules and modified loads.
2. Provide cut sheets for new dimmers to be used.Identify which circuits will be used by which dimmers.
3. Show on plan which lights will be on which zone.
4. Sheet E201, Identify circuits to all power being relocated or added, provide panel locations, schedules and modified loads.
5. Provide the same as #4 for sheets E210 and E400.

Ray Majuta,Elect Plan Review,
PDSD, City of Tucson,
1/17/11,
Ray.Majuta@tucsonaz.gov
12/21/2010 GERRY KOZIOL WWM REVIEW Approved
12/22/2010 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/07/2011 SUE REEVES OUT TO CUSTOMER Completed
02/07/2011 SUE REEVES REJECT SHELF Completed