Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM03519
Parcel: 11204409A

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM

Permit Number - T10CM03519
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2011 PAUL MACHADO ENGINEERING REVIEW Denied Bldg. plans cannot be aproved prior to the approval of the Site plan. PM. 01-03-11.
01/19/2011 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 1-19-2011
Activity: T10CM03519
Address: 2901 E Blacklidge
Applicant: Quatro Vest. Inc.

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings and one set of the first submission for reference. All corrections and revisions shall be made on original tracings or finished reproducible set. Pencil and/or white out on final prints will not be acceptable. To expedite review, please cloud the originally submitted set with red ink and limit clouding on final set. Ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

SITE PLAN:
2. Specify the location of all utility lines and service meters, R106.1.1.

STRUCTURAL PLAN:
3. Specify connection method for all second floor braced wall panels at end points for sufficient load path to wall bracing below.

PLUMBING PLAN:
4. Provide both a gray water and blackwater drains from the washing machine.
5. Gray water discharge from the washing machine must terminate directly out wall above grade.
6. Provide note requiring that water hammer arrestors be installed in accordance with ASSE 1010-2004 on water lines serving appliances equipped with quick-closing valves to include but not limited to: clothes washers, dishwashers, and refrigerators, UPC 609.10.
7. Waste and vent isometric needs to show segregated drain lines for gray water ordinance.
8. Provide a complete water supply distribution plan for review.

MECHANICAL PLAN:
9. Show the secondary condensate line discharging to an obvious location, M1411.3.

ELECTRICAL PLAN:
10. Show receptacle outlets at wall spaces 2' or more so that no point along the wall (excluding door openings) is more than 6' from a receptacle outlet, E3801.2.

OUTDOOR LIGHTING CODE
11. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style).

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review
12/21/2010 ANDREW CONNOR NPPO REVIEW Denied Site plan approval necessary to continue review.
12/22/2010 MICHAEL ST. PAUL ZONING REVIEW Denied Site plan approval required. See comments for T10CM03518 for site plan.
12/30/2010 GERRY KOZIOL WWM REVIEW Denied NEED WW CREDIT EVALUATION- 5TH FLOOR
NEED REVIEW/APPROVAL FOR CAPACITY EVALUATION AND/OR POINT/METHOD OF CENNECTION
Due to accessibility to sewer, applicant may be asked to connect directly to8" main depending on capacity of 4" line. TO BE REVIEWED BY COT AND WWM ORDINANCES.
REVIEW BY PCRWRD DEV LIASON UNIT 3RD FL PWB- 740-6534