Permit Number: T10CM03512
Parcel: 114540640

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T10CM03512
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/28/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
12/28/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide the balancing data for the activity.
12/28/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
12/28/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
12/28/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/28/2010 ROBERT SHERRY WATER REVIEW Approved
12/28/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The maximum length for a 2" trap arm is 5'-0" (P3)
2. Provide a water supply for the point of use water dispenser.
3. Indicate the termination point of the pressure relief from WH-1.