Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T10CM03512
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/20/2010 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 12/21/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/21/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the sequence of operation for the new restroom exhaust fan. 2. Complete the ventilation calculations. 3. Show how (or if) the supply diffusers located in the restrooms are connected to the HVAC ductwork.4. Provide the balancing data for the activity. 4. Show the minimum R-value for the duct insulation. 5. Provide a return grille for the massage room. |
| 12/21/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. No more than one trap may be on a trap arm (P6). 2. Provide a vent for each trap (P3). 3. Provide cleanouts sized per Section 707.11, UPC 2006. 4. Clarify the purpose of the existing 40-gallon water heater - no water pipng is shown attached to it. 5. Show the return hot water piping. 6. Provide specifications for the drinking fountains. 7. Relocate the cleanout for P5 to be located in an accessible position. 8. Coordinate the location of the vent for P3 in the men's shower room. 9. Provide specifications for the shower valves. 10. Show the water supply pipe for the suite. |
| 12/21/2010 | ROBERT SHERRY | WATER | REVIEW | Denied | What is the source of water for this activity? Provide the location and size of the water meter and backflow preventer along with the connected demand on the meter. |
| 12/22/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A-2; DETAIL 4: LOCATE PAPER DISPENSER PER ICC/ANSI A117.1-2003 FIGURE 604.7(a). 2. SHEET A-2; ENLARGED PLAN 3: SHOW AN ELEVATION OF THE HIGH/LOW DRINKING FOUNTAIN PER ICC/ANSI. 3. SHEET A-2; FLOOR PLAN: IS THIS A PRELIMINARY PLAN? NEED A FINAL. |
| 12/22/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project:T10CM03512 8868 E Tanque Verde Electrical plans denied for the following: 1. The notes on sheet E0.1 indicate wiring to be per NEC 517 (Patient Care Area) ? 2. The water heater in the plumbing plan shows a 208/3 phase 4500 nwatt 50 gallon, the panel schedule shows an existing one only 2/pole 1500 watt? 3. The circuits for power need to be numbered on the power plan, and the new fans and lights need to be circuited and loads included on the panel scheduled. 4. Show Panel A on the Service, and any other services on the Main Service. 5. Show the location of the main service. Plans are very incomplete. Ray T Majuta Electrical Plan Review, PDSD, City of Tucson, 12/22/10, Ray>majuta@tucsonaz.gov |
| 12/22/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/22/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 12/22/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 12/28/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/28/2010 | CPIERCE1 | ZONING | REVIEW | Needs Review |