Permit Number: T10CM03509
Parcel: 137055230

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T10CM03509
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/05/2011 ROBERT SHERRY WATER REVIEW Approved
01/05/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the purpose of the 3-compartment sink located in room 184 with regard to the waste connections. If each compartment is used to process food or ice for human consumption or to sanitize food-serving plates and utensils, an indirect connection is appropriate; otherwise, provide direct connections to the sewer system. Reference: Sections 304.0, 704.3, and 801.2, UPC 2006.
2. Provide upper terminal cleanouts on horizontal drainage pipe over 5 feet in length (horizontal drain lines serving sinks and urinals require cleanouts regardless of length). Reference: Section 707.4, UPC 2006.
3. Clarify the installation of the floor drain in room 185. Does the "existing waste piping" include a vent and a cleanout? Reference: Sections 103.2.3, 707.4, and 901.0, UPC 2006.
01/05/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The new dehumidifying unit (DHU-9) does not introduce any outdoor air into the building. Show that adequate ventilation is still being supplied to the building. Reference: Sections 102.4 and 401.2, IMC 2006 and Section 1202.2.1, UBC 1994.
01/11/2011 GERRY KOZIOL WWM REVIEW Denied NEED WW CREDIT EVALUATION FROM 5TH FLOOR.
01/14/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/21/2010 DAVE MANN FIRE REVIEW Approved
12/21/2010 RONALD BROWN ZONING HC REVIEW Passed Reference Building Comments

Final Status

Task End Date Reviewer's Name Type of Review Description
01/19/2011 CPIERCE1 OUT TO CUSTOMER Completed
01/19/2011 SUE REEVES REJECT SHELF Completed