Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T10CM03499
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/20/2010 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
12/20/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide ventilation calculations. Reference: section 403.3, IMC 2006. 2. Revise the exhaust fan control so that the exhaust fan operates whenever the A/C supply air is delivered to the restroom. |
12/20/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/20/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
12/20/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/20/2010 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
12/20/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
12/20/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
12/20/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
12/20/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
12/20/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
12/21/2010 | GERRY KOZIOL | WWM | REVIEW | Approved |