Permit Number: T10CM03494
Parcel: 141013700

Address:
5173 S ZENITH WY

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T10CM03494
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2011 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T10CM03494
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
Show corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

SITE PLAN:

1. Indicate the location of the electric service panel, R106.1.1.

SECTIONS - DETAILS:

1. Clarify the location of each door ID (D01, 02 & 03) on the floor plan, R106.1.1.
2. Clarify if keynote #4 is correctly shown on the West Elevation, R106.1.1.
3. Clarify if the sliding door on the North elevation is existing or a window replacement.
4. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c ceiling framing, IRC table R702.3.5 footnote d.
5. Provide roof scupper locations with crickets for roof drainage, R903.4.

MECHANICAL PLANS:

1. Show a minimum 2' chimney (metal flue) termination above any roof point within 10' measured horizontally, G2427.5.3. The chimney height may be determined by the garage parapet top if within 10' of the chimney.

ELECTRICAL PLANS:

1. Clarify the location of the existing 100A panel on the Electrical Plan, E3501.6.2 & E3605.8. The new panel location may require sizing and placement of a new feeder from the main service panel.
2. Provide a panel schedule showing wire size of each circuit or notate the wire size for each protection rating, E3602.2.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
12/28/2010 MICHAEL ST. PAUL ZONING REVIEW Denied Provide a copy of the last approved plot plan (T01CM04236).

Fully dimension the new site plan (see plot plan hadout).

Final Status

Task End Date Reviewer's Name Type of Review Description
01/24/2011 CPIERCE1 OUT TO CUSTOMER Completed
01/24/2011 SUE REEVES REJECT SHELF Completed