Permit Number: T10CM03490
Parcel: 11446027E

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T10CM03490
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
01/06/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project:T10CM03490
7671 E Tanque Verde
87.096 KV Photovoltaic System

The electrical plans have been denied for the following:

1. Provide a 3 line diagram of the system in addition to the one lines you have provided. Show the grounding electrode conductor run independently from other conductors, from the AC grounding electrode of the system to the Inverters and show the size of this conductor.


Ray T Majuta,
PDSD, City of Tucson,
Elect Plan Ck,
1/08/11
Ray.Majuta@tucsonaz.gov
12/17/2010 DAVE MANN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/13/2011 GERARDO BONILLA OUT TO CUSTOMER Completed
01/13/2011 SUE REEVES REJECT SHELF Completed