Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T10CM03490
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/05/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/06/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project:T10CM03490 7671 E Tanque Verde 87.096 KV Photovoltaic System The electrical plans have been denied for the following: 1. Provide a 3 line diagram of the system in addition to the one lines you have provided. Show the grounding electrode conductor run independently from other conductors, from the AC grounding electrode of the system to the Inverters and show the size of this conductor. Ray T Majuta, PDSD, City of Tucson, Elect Plan Ck, 1/08/11 Ray.Majuta@tucsonaz.gov |
| 12/17/2010 | DAVE MANN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/13/2011 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 01/13/2011 | SUE REEVES | REJECT SHELF | Completed |