Review Date Reviewer's Name Type of Review Description Status Comments
10/25/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T10CM03485
2245 N 13 AV #02

Electrical pland denied for following:
1. Cover sheet shows new 50 amp circuit to new sub-panel--
see sheet 1 for load calc's, however sheet 1 says on top of panel that it is existing ? Also all new panels need to show location they will be installed for record.
2. Cover sheet shows 100 amp cb to Sub-Panel at office, see sheet 3 for load calc's----sheet 3 the panel is shown at load of 103 amps, must be below 100 amps.
3.Cover sheet shows a 150 amp cb to Panel at Bldg 2 -see
sheet 2, the totals for phase A=28795 va+phase B 26992 va
totaling 55787 va, 55787 va divided by 240= 232 amps ?
Panel identification confusing,and total load calc's incorrect. The panels loads for a sub panel in sheet 2 is the same as total panel loads for office panel sheet 3 ?
Please clear up.

Ray Majuta
Elect Plan Review
PDSD,Cof T
10/25/11