Review Details: REVISION - - 2ND
Permit Number - T10CM03485
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/25/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T10CM03485 2245 N 13 AV #02 Electrical pland denied for following: 1. Cover sheet shows new 50 amp circuit to new sub-panel-- see sheet 1 for load calc's, however sheet 1 says on top of panel that it is existing ? Also all new panels need to show location they will be installed for record. 2. Cover sheet shows 100 amp cb to Sub-Panel at office, see sheet 3 for load calc's----sheet 3 the panel is shown at load of 103 amps, must be below 100 amps. 3.Cover sheet shows a 150 amp cb to Panel at Bldg 2 -see sheet 2, the totals for phase A=28795 va+phase B 26992 va totaling 55787 va, 55787 va divided by 240= 232 amps ? Panel identification confusing,and total load calc's incorrect. The panels loads for a sub panel in sheet 2 is the same as total panel loads for office panel sheet 3 ? Please clear up. Ray Majuta Elect Plan Review PDSD,Cof T 10/25/11 Ray.majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/26/2011 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 10/26/2011 | SUE REEVES | REJECT SHELF | Completed |