Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T10CM03485
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/05/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T10CM03485 2245 N th Av #2 Denied for the following: Previous plans have been stamped by an electrical engineer, these also have to be stamped since they are a revision to previous plans. Explain why these revisions are being made, where do new circuits supply, and where would this new panel be located ? Why a change to a 400 Main ? These questions sholud be addressed on the plan. Ray T Majuta, Elect Plan Ck, PDSD, C of Tucson, 10/5/2011 Ray.majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/20/2011 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 10/20/2011 | SUE REEVES | REJECT SHELF | Completed |