Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T10CM03485
2245 N th Av #2

Denied for the following:
Previous plans have been stamped by an electrical engineer, these also have to be stamped since they are a revision to previous plans.
Explain why these revisions are being made, where do new circuits supply, and where would this new panel be located ? Why a change to a 400 Main ?
These questions sholud be addressed on the plan.

Ray T Majuta,
Elect Plan Ck,
PDSD, C of Tucson,
10/5/2011