Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T10CM03485
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | Please provide a structural connection detail showing existing structure and new panel standoff anchorage with 5/16" lag bolts. |
| 01/06/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10CM03485 2245 N 13th St #2 19.152 Photovoltaic Sys The electrical plans have been denied for the following: 1. The minimum size for lettering is 3/32", as required by this department. Resubmit plans in this size please. Everything else approved, once correct size received I can stamp and approve them. Ray T Majuta, Electrical Plan Check, PDSD City of Tucson, 1/8/11, Ray.Majuta@tucsonaz.gov |
| 12/17/2010 | DAVE MANN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/12/2011 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 01/12/2011 | SUE REEVES | REJECT SHELF | Completed |