Permit Number: T10CM03484
Parcel: 117050480

Address:
411 N 4TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM03484
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/21/2010 DAVE MANN FIRE REVIEW Approved
12/30/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET PV2; ROOF FRAMING LAYOUT: PER THE CITY OF TUCSON STANDARDS, INCREASE THE LETTERING HEIGHT TO A MINIMUM OF 3/32" AT THE DIMENSION LINE AND AT THE BUILDING SECTION CUTS.
2. SHEET PV2; ARRAY PROFILE: PER THE IBC SECTION 1013.5, A 42" HIGH GUARD RAIL IS REQUIRED WHERE "COMPONENTS THAT REQIRE SERVICE ARE LOCATED WITHIN 10 FEET OF A ROOF EDGE". REVISE.
3. GENERAL: ALL SHEETS MUST BE STAMPED, SIGNED, AND DATED BY A LICENSED PROFESSIONAL. SEE SHEETS PV0 AND PV1.1.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/04/2011 CPIERCE1 OUT TO CUSTOMER Completed
01/04/2011 SUE REEVES REJECT SHELF Completed