Permit Number - T10CM03481
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/17/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10CM03481 7671 E Tanque Verde The Electrical Plans have been denied for the following items: 1. Sheet E2.1, the SES2 feed to item #1, has a 100 amp fuse with 3# 4's and #10 grd which should be a #8 grd. The SES2 feeds to items #2 have 60 amp fuses, the feeder conductors are # 10, thus the fuses should be 30 amp Circuits BP 1,2,3 and 4 show #2 with #12 grd feeders under a 20 amp fuse, should be # 12 feeders also. Under Switchgear MDP1, the feeder to SP1 shows 3 #8's with #10 grd fused at 100 amp. Switchgear MDP1 feeder to HWRP1 shows # 12 conductors under 30 amps ? Could be correct. Ray Majuta C of T, PDSD, Elect Pln Ck, 2/22/11 |