Permit Number: T10CM03478
Parcel: 11717023E

Address:
88 E BROADWAY BL

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T10CM03478
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2011 STEVE SHIELDS ZONING REVIEW Approved
01/03/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/20/2010 ELIZABETH LEIBOLD ENGINEERING REVIEW Approved
12/20/2010 RONALD BROWN ZONING HC REVIEW Passed Reference Building Comments
12/20/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
12/23/2010 STANTEC ELECTRICAL-COMMERCIAL REVIEW Approved
12/27/2010 GERRY KOZIOL WWM REVIEW Approved
12/27/2010 DAVE MANN FIRE REVIEW Approved
12/30/2010 ROBERT SHERRY WATER REVIEW Approved
12/30/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide an indirect waste from the counter-mounted ice makers, terminating with an air gap. Reference: Section 802.1, IPC 2006.
2. Clarify the modifications to the combination waste and vent system; the system does not appear on the riser diagram on sheet p3.1 (key notes 11, 23, and 24).
3. Clarify the nature of the "soda fountain" noted in room 259 with respect to the type of backflow protector required (sheet 2-p1.1). Reference: Section 608.16.1, IPC 2006, as amended by the City of Tucson.
12/30/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/03/2011 CPIERCE1 OUT TO CUSTOMER Completed
01/03/2011 SUE REEVES REJECT SHELF Completed