03/24/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S3.0; STRUCTURAL CALCULATIONS (SHEET 17): THE GUARD RAIL ASSEMBLY IN THE CALCULATIONS DOES NOT SHOW UP ON THE DRAWINGS. VERIFY AND ADD TO THE DRAWINGS.
2. SHEET S3.0 (DETAIL 2); STRUCTURAL CALCULATIONS (SHEET 10): THE CALCULATIONS FOR THE CONTINUOUS FOOTING INDICATE 1'-6" WIDE, WHILE THE DRAWING DETAIL INDICATES 1'-0" WIDTH. CLARIFY.
3. SHEET S3.0; DETAIL 2: REVISE THE TITLE ON THIS DETAIL.
4. SHEET S3.0; DETAIL 3: PROVIDE DIMENSIONS ON THE DETAIL TO LOCATE THE DEPTH OF THE FOOTING BELOW THE SLAB/FINISH GRADE.
5. SHEET S3.0: PROVIDE A DETAIL FOR THE WOOD COLUMN C1 CONNECTION TO THE FOUNDATION.
6. SHEET S3.0; DETAIL 11: PROVIDE THE RISER HEIGHT AND THE TREAD WIDTH ON THE DETAIL.
7. STRUCTURAL CALCULATIONS; PAGE 8: WHERE IS THIS MC10X28.5 LOCATED? IT IS NOT CALLED OUT ON THE PLAN OR IN A DETAIL. PROVIDE.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.