Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T10CM03461
Review Name: REVISION - - 3RD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/24/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET S3.0; STRUCTURAL CALCULATIONS (SHEET 17): THE GUARD RAIL ASSEMBLY IN THE CALCULATIONS DOES NOT SHOW UP ON THE DRAWINGS. VERIFY AND ADD TO THE DRAWINGS. 2. SHEET S3.0 (DETAIL 2); STRUCTURAL CALCULATIONS (SHEET 10): THE CALCULATIONS FOR THE CONTINUOUS FOOTING INDICATE 1'-6" WIDE, WHILE THE DRAWING DETAIL INDICATES 1'-0" WIDTH. CLARIFY. 3. SHEET S3.0; DETAIL 2: REVISE THE TITLE ON THIS DETAIL. 4. SHEET S3.0; DETAIL 3: PROVIDE DIMENSIONS ON THE DETAIL TO LOCATE THE DEPTH OF THE FOOTING BELOW THE SLAB/FINISH GRADE. 5. SHEET S3.0: PROVIDE A DETAIL FOR THE WOOD COLUMN C1 CONNECTION TO THE FOUNDATION. 6. SHEET S3.0; DETAIL 11: PROVIDE THE RISER HEIGHT AND THE TREAD WIDTH ON THE DETAIL. 7. STRUCTURAL CALCULATIONS; PAGE 8: WHERE IS THIS MC10X28.5 LOCATED? IT IS NOT CALLED OUT ON THE PLAN OR IN A DETAIL. PROVIDE. 8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/04/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 04/04/2011 | SUE REEVES | REJECT SHELF | Completed |