Permit Number: T10CM03421
Parcel: 12801005H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM03421
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 9; SHEET A-803; DETAIL E7: PROVIDE STRUCTURAL CALCULATIONS OF THE LOAD CAPACITY OF THE EXISTING JOISTS WITH THE ADDED TRANSFORMER WEIGHT. A NOTE WAS ADDED TO THIS DETAIL, INDICATING "ELECTRICAL TRANSFORMER MAX. WEIGHT W/ PLATFORM NOT TO EXCEED ACCEPTABLE LOAD TOLERANCE TO EXISTING STRUCTURE". THIS IS NOT AN ACCEPTABLE RESPONSE. WHO WILL DECIDE WHAT THAT "ACCEPTABLE LOAD TOLERANCE" OF THE EXISTING STRUCTURE IS? THE ENGINEER OR ARCHITECT OF RECORD MUST PROVIDE A CALCULATION CLEARLY INDICATING THAT THE EXISTING JOISTS CAN SAFELY SUPPORT THE NEW TRANSFORMER LOAD. IN THE CALCULATION, INCLUDE THE EXISTING JOIST SIZE, THE TRANSFORMER WEIGHT, AND THE TRANSFORMER LOCATION. PROVIDE THE INFORMATION ON DETAIL E7 AS REQUIRED.
2. GENERAL: PROVIDE A WRITTEN RESPONSE TO THIS REVIEW COMMENT.
01/24/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
01/25/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved; delete the orphaned note calling for an RPZ prior to the water meter on the water riser diagram.[If the reduced pressure zone backflow prevention assembly shown preceding the landlord's water meter is required by the landlord, provide details showing the access and clearance requirements for the backflow assembly, as required by Section 603.3.4, UPC 2006.]
2. Comment not resolved; a vacuum breaker is not required, a vacuum relief valve is required. (Note that detail 3/P-201 is not coordinated with either the plumbing partial plan or the water riser diagram.) [Provide a vacuum relief for storage-type water heaters located above any fixture outlets; installed per the manufacturer's listing requirements. Reference: Sections 310.4 and 608.7, UPC 2006.]
01/25/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved; the calculations shown on sheet M-003 are not from Section 403.3, IMC 2006 nor are they from ASHRAE 62.1-2004. In addition, the maximum supply air shown on both charts does not correspond to the scheduled airflow for the existing rooftop units. [Section 403.3, IMC 2006, as amended by the City of Tucson allows the use of the ASHRAE 62-1-2004 ventilation calculation procedure provided that the default occupant densities and combined outdoor air rates are used.]

Final Status

Task End Date Reviewer's Name Type of Review Description
02/10/2011 DELMA ROBEY OUT TO CUSTOMER Completed
02/10/2011 SUE REEVES REJECT SHELF Completed