Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM03421
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T10CM03421
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 5870 E Broadway Bl, #152
T10CM03421

Commercial Submittal Requirements, minimum size lettering 3/32". Resubmit with correct lettering size.
All other electrical ok, will approve once resubmitted.

Ray Majuta,
Elect Plan Review,
PDSD,City of Tucson,
1/04/11
Rat.Majuta@tucsonaz.gov
12/10/2010 DAVE MANN FIRE REVIEW Approved
12/17/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A-001; DRAWING INDEX: REVISE THE STRUCTURAL SHEET NUMBERS TO MATCH.
2. SHEET A-101: CITY OF TUCSON STANDARDS REQUIRE ALL LETTERING TO BE A MINIMUM HEIGHT OF 3/32". REVISE DEMOLITION, BARRICADE DETAIL NOTES, AND KEY NOTES.
3. SHEETS A-101, A-102, A-111, A-112, A-121, AND A-122; KEY NOTES: REMOVE KEY NOTES ON EACH SHEET THAT ARE NOT PERTINENT TO THAT SPECIFIC SHEET.
4. SHEET A-102: CITY OF TUCSON STANDARDS REQUIRE ALL LETTERING TO BE A MINIMUM HEIGHT OF 3/32". REVISE DEMOLITION AND KEY NOTES.
5. SHEET A-801; DETAIL E7: A DETAIL NOTE INDICATES THE CONNECTION AT THE TOP OF THE BRACE PER E1/A-801. IS THIS CORRECT? VERIFY.
6. SHEET A-801; DETAIL E7: PROVIDE THE SIZE AND QUANTITY OF CONNECTORS AT THE BRACE AND THE SIZE AND SPACING OF THE BRACES.
7. SHEET A-802; DETAIL E1: A DETAIL NOTE INDICATES A CONNECTION OF THE BRACING PER E7-801. IS THIS CORRECT? VERIFY.
8. SHEET A-803; DETAIL E7: HOW IS THE REINFORCEMENT ANGLE CONNECTED TO THE EXISTING JOIST? VERIFY.
9. SHEET A-803; DETAIL E7: PROVIDE STRUCTURAL CALCULATIONS OF THE LOAD CAPACITY OF THE EXISTING JOISTS WITH THE ADDED TRANSFORMER WEIGHT.
10. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/20/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
12/23/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 106.1.1, IBC 2006.
2. Section 403.3, IMC 2006, as amended by the City of Tucson allows the use of the ASHRAE 62-1-2004 ventilation calculation procedure provided that the default occupant densities and combined outdoor air rates are used.
12/23/2010 ROBERT SHERRY WATER REVIEW Approved
12/23/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. If the reduced pressure zone backflow prevention assembly shown preceding the landlord's water meter is required by the landlord, provide details showing the access and clearance requirements for the backflow assembly, as required by Section 603.3.4, UPC 2006.
2. Provide a vacuum relief for storage-type water heaters located above any fixture outlets; installed per the manufacturer's listing requirements. Reference: Sections 310.4 and 608.7, UPC 2006.
3. Clarify the installation of a vacuum breaker shown on the hot water supply from the water heater in detail 3/P-201. Reference: section 103.2.3, UPC 2006.
12/29/2010 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/13/2011 SUE REEVES APPROVAL SHELF Completed
01/13/2011 DELMA ROBEY OUT TO CUSTOMER Completed