Permit Number: T10CM03412
Parcel: 11716029A

Address:
103 E ALAMEDA ST

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T10CM03412
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
12/09/2010 DAVE MANN FIRE REVIEW Approved
12/21/2010 RONALD BROWN ZONING HC REVIEW Passed Reference Building Comments
12/21/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A0.1; GENERAL NOTES: CITY OF TUCSON STANDARDS REQUIRE ALL LETTERING TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. DIMENSIONS ARE DARK AND HARD TO READ. REVISE.
2. SHEET A1.0; FIRST FLOOR PLAN: CITY OF TUCSON STANDARDS REQUIRE ALL LETTERING TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. DIMENSIONS ARE DARK AND HARD TO READ. REVISE.
3. SHEET A1.1; ALL PLANS: CITY OF TUCSON STANDARDS REQUIRE ALL LETTERING TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. DIMENSIONS ARE DARK AND HARD TO READ. REVISE.
4. SHEET A2.0; PLAN: CITY OF TUCSON STANDARDS REQUIRE ALL LETTERING TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. DIMENSIONS ARE DARK AND HARD TO READ. REVISE.
5. SHEET A3.0; SECTION AND ELEVATION: CITY OF TUCSON STANDARDS REQUIRE ALL LETTERING TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. DIMENSIONS ARE DARK AND HARD TO READ. REVISE.
6. SHEET A4.0; STAIR PLAN: CITY OF TUCSON STANDARDS REQUIRE ALL LETTERING TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. DIMENSIONS ARE DARK AND HARD TO READ. REVISE.
7. SHEET A4.0; DETAIL 13: CITY OF TUCSON STANDARDS REQUIRE ALL LETTERING TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. DIMENSIONS ARE DARK AND HARD TO READ. REVISE.
8. SHEET A4.0; DETAIL 21: CITY OF TUCSON STANDARDS REQUIRE ALL LETTERING TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. DIMENSIONS ARE DARK AND HARD TO READ. REVISE.
9. SHEET A4.0; DETAIL 23: CITY OF TUCSON STANDARDS REQUIRE ALL LETTERING TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. DIMENSIONS ARE DARK AND HARD TO READ. REVISE.
10. GENERAL: THE SPECIAL INSPECTOR LISTED (RANDY HAMILTON, PE) IS NOT ON THE CITY OF TUCSON'S APPROVED LIST OF CERTIFIED INSPECTORS. CONTACT LEERAY HANLY AT LEERAY.HANLY@TUCSONAZ.GOV FOR INFORMATION CONCERNING SPECIAL INSPECTORS.
11. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/23/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 3/32-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
2. Condensate drains may not terminate in an area that is not capable of absorbing the condensate flow without surface drainage (e.g. the roof). Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson.
12/30/2010 TERRY STEVENS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/11/2011 CPIERCE1 OUT TO CUSTOMER Completed
01/11/2011 SUE REEVES REJECT SHELF Completed