Permit Number: T10CM03411
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T10CM03411
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/08/2010 TERRY STEVENS ZONING REVIEW Approved
12/08/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 106.1.1, IBC 2006.
12/08/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10cm03411

1. Font size must be min 3/32'' per submittal requirements .
2. Sumbit for review,too large for counter walk-thur.

Ray T Majuta,
Elect Pln CK,City of Tucson,
12/08/10
Ray.Majuta@tucsonaz.gov
12/08/2010 ROBERT SHERRY WATER REVIEW Approved
12/08/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 106.1.1, IBC 2006.
12/08/2010 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
12/08/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 106.1.1, IBC 2006.
12/08/2010 PAUL MACHADO ENGINEERING REVIEW Approved
12/08/2010 MARTIN BROWN FIRE REVIEW Approved
12/08/2010 RONALD BROWN ADA REVIEW Passed
12/08/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/08/2010 RONALD BROWN ZONING HC REVIEW Approved