Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM03374
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/10/2010 | CPIERCE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
12/10/2010 | CPIERCE1 | ZONE H/C | REVIEW | Needs Review | |
12/17/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PLEASE PROVIDE LIGHTING LOAD CALCULATIONS TO VERIFY COMPLIANCE WITH IECC SECTION 505.5. IT APPEARS THAT CURRENT CONFIGURATION OF LIGHTING EXCEEDS ALLOWANCES. PLEASE PROVIDE REQUIRED AIC RATINGS FOR EQUIPMENT. WHILE NOT A VIOLATION OF CODE AND NOT A REQUIRED CORRECTION, PLEASE VERIFY THAT KEYNOTES 3 AND 7 PP E3 REFLECT CORRECT WIRE SIZES WANTED BY ENGINEER OF RECORD. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/11/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |
01/11/2011 | SUE REEVES | REJECT SHELF | Completed |