Permit Number: T10CM03374
Parcel: 12801005H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM03374
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/10/2010 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review
12/10/2010 CPIERCE1 ZONE H/C REVIEW Needs Review
12/17/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied PLEASE PROVIDE LIGHTING LOAD CALCULATIONS TO VERIFY COMPLIANCE WITH IECC SECTION 505.5. IT APPEARS THAT CURRENT CONFIGURATION OF LIGHTING EXCEEDS ALLOWANCES.

PLEASE PROVIDE REQUIRED AIC RATINGS FOR EQUIPMENT.

WHILE NOT A VIOLATION OF CODE AND NOT A REQUIRED CORRECTION, PLEASE VERIFY THAT KEYNOTES 3 AND 7 PP E3 REFLECT CORRECT WIRE SIZES WANTED BY ENGINEER OF RECORD.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/11/2011 CPIERCE1 OUT TO CUSTOMER Completed
01/11/2011 SUE REEVES REJECT SHELF Completed