Permit Number: T10CM03374
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T10CM03374
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/03/2010 STEVE SHIELDS ZONING REVIEW Approved
12/03/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/03/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
12/03/2010 ROBERT SHERRY WATER REVIEW Approved
12/03/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET D1 (DEMOLITION PLAN); SHEET A1 (FLOOR PLAN): AT THE RESTROOM, THE DEMOLITION PLAN INDICATES EXISTING PARTITIONS, DOOR AND FIXTURE TO REMAIN AS-IS. HOWEVER, PLAN A1 NOTE INDICATES NEW FIXTURES. CLARIFY.
2. SHEET A3A; INTERIOR ELEVATION L (#2): ADD A VERTICAL GRAB BAR PER ICC/ANSI A117.1-2003, FIGURE 604.5.1.
12/03/2010 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
12/03/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/03/2010 BIANCA RAMIREZ ENGINEERING REVIEW Approved
12/03/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/03/2010 ERIC NEWCOMB ADA REVIEW Passed
12/03/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
12/10/2010 DAVE MANN FIRE REVIEW Approved