Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM03371
Parcel: 137055330

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM03371
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2011 GERRY KOZIOL WWM REVIEW Denied Need type III capacity letter from 3rd floor PWB- Kurt Stemm
01/06/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved. The specification contains multiple lavatory faucets for the counter-mounted lavatories but not all of the choices are capable of limiting the delivery temperature. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
2. Comment not resolved; the specification does not indicate that the shower control valves are listed to ASSE Standard 1016. Provide information to show that the shower and tub/shower control valves conform to the requirements of ASSE 1016. Reference: Section 418.0, UPC 2006.
3. Comment not addressed. The specified model (Eemax SP2412) for the instantaneous water heater, WH-3, is not capable of being set to limit the delivered water temperature. Provide an instantaneous water heater that is listed for controlling the water temperature or show how the temperature of the hot water supply to the public lavatory is to be controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
4. Comment not resolved; revise the waste and vent schematic as needed. Provide cleanouts sized per Section 707.11, UPC 2006 (e.g. the women's dressing room and the men's showers).
5. In two locations, the waste and vent schematic on sheet P-3 appears to show a trench drain and a floor drain sharing one trap and trap arm. Each fixture shall be separately trapped. Reference: Section 1001.1, UPC 2006.
01/06/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/29/2010 ERIC NEWCOMB ZONE H/C REVIEW Approved
12/29/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approv-Cond 1. PROVIDE A REVISED SHEET A2.1 THAT IS STAMPED, SIGNED, AND DATED BY THE ARCHITECT OF RECORD. REMOVE "PRELIMINARY" NOTE.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/10/2011 CINDY AGUILAR OUT TO CUSTOMER Completed
01/10/2011 SUE REEVES REJECT SHELF Completed