Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10CM03371
Parcel: 137055330

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T10CM03371
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/03/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
12/03/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
12/03/2010 GBONILL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
12/03/2010 ROBERT SHERRY WATER REVIEW Denied A demand flow of 100 GPM through a 2" water meter results in an excessive pressure drop and a velocity greater than the maximum 8 FPS allowed for either plastic or copper piping. In addition, Tucson Water limits the 2" meter to a maximum demand of 80 GPM. Reference: Sections 610.2 and 610.12, UPC 2006 and COT Backflow Prevention Ordinance, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
12/03/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Needs Review
12/03/2010 GBONILL1 WWM REVIEW Needs Review
12/03/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
12/03/2010 PAUL MACHADO ENGINEERING REVIEW Approved
12/03/2010 MARTIN BROWN FIRE REVIEW Approved
12/03/2010 RONALD BROWN ADA REVIEW Passed
12/03/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
12/03/2010 RONALD BROWN ZONING HC REVIEW Needs Review