Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T10CM03355
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/07/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 02/09/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not resolved. The waste and riser diagram now shows two trap arms for the directly-connected compartments of the 3-compartment sink combining prior to the vent. Section 1001.1, UPC 2006 allows only one trap on a trap arm. Section 1001.2, UPC 2006 allows one trap to serve two sinks but this is done using a continuous waste from one of the sinks, joining at the tailpiece of the sink having the trap. [Comment not resolved. The waste and vent riser diagram on sheet P3.0 appears to show three trap arms combining at the location of the 3-compartment sink (apparently the wash and rinse compartments and another sink located near the dishwasher). Reference: Sections 1001.1 and 1001.2, UPC 2006. [Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006.]] |
| 02/10/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/10/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/17/2011 | DROBEY1 | ZONING | REVIEW | Needs Review | |
| 02/17/2011 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/17/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |