12/01/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
12/01/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the sequence of operation for the restroom exhaust fans (i.e. tied to room lights) so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
12/01/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM03331
340 W AJO

Denied, the exhaust fans in the restrooms are required to come on any time air is supplied to the room. See Mechcanical Plan Reviewer comments. Need to review how this will be accomplished electrically, everything else ok.

Ray T Majuta,
Elect Pln CK,
12/1/10
12/01/2010 ROBERT SHERRY WATER REVIEW Approved
12/01/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Clarify area of project at detail B/A0. This does not relative to floor plan.
2. At detail 1/A1, provide lateral bracing to structure above as required by 2006 IBC, Section 1607.13, 5 psf lateral load.
3. For future clarification, generic accessible details will not be accepted. Please provide all required accessibile dimensions and equipment on the floor plan and actual designed interior elevations in compliance with the 2006 IBC, Chapter 11 and ICC (ANSI 117.1).
4. Please delete all references to ADA. Accessibility for this project is governed by the 2006 IBC, Chapter 11 and ICC (ANSI 117.1).
12/01/2010 PAUL MACHADO ENGINEERING REVIEW Approved
12/01/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a waste and vent riser diagram to show the new mop sink is to be installed.
12/01/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/01/2010 RONALD BROWN ADA REVIEW Passed
12/01/2010 RONALD BROWN ZONING HC REVIEW Denied Reference Building Comments
12/03/2010 DROBEY1 WWM REVIEW Needs Review
12/03/2010 DROBEY1 FIRE REVIEW Needs Review