Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T10CM03331
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/01/2010 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/01/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom exhaust fans (i.e. tied to room lights) so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006. |
| 12/01/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10CM03331 340 W AJO Denied, the exhaust fans in the restrooms are required to come on any time air is supplied to the room. See Mechcanical Plan Reviewer comments. Need to review how this will be accomplished electrically, everything else ok. Ray T Majuta, Elect Pln CK, 12/1/10 |
| 12/01/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/01/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Clarify area of project at detail B/A0. This does not relative to floor plan. 2. At detail 1/A1, provide lateral bracing to structure above as required by 2006 IBC, Section 1607.13, 5 psf lateral load. 3. For future clarification, generic accessible details will not be accepted. Please provide all required accessibile dimensions and equipment on the floor plan and actual designed interior elevations in compliance with the 2006 IBC, Chapter 11 and ICC (ANSI 117.1). 4. Please delete all references to ADA. Accessibility for this project is governed by the 2006 IBC, Chapter 11 and ICC (ANSI 117.1). |
| 12/01/2010 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 12/01/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a waste and vent riser diagram to show the new mop sink is to be installed. |
| 12/01/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/01/2010 | RONALD BROWN | ADA | REVIEW | Passed | |
| 12/01/2010 | RONALD BROWN | ZONING HC | REVIEW | Denied | Reference Building Comments |
| 12/03/2010 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 12/03/2010 | DROBEY1 | FIRE | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/03/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |